Touch protection according to EN 61800-5-1: For the intended purpose
Compliance with standards
Standards EN 60146-1-1, EN 61800-2, EN 61800-3, EN 61800-5-1, EN 60204-1, EN 60529
UL61800-5-1, CSA 22.2 No. 274-13
CE marking In accordance with EMC Directive No. 2014/30/EU and Low-Voltage Directive No. 2014/35/
EU
Radio interference suppres‐
sion
In accordance with the EMC product standard for variable-speed drives EN 61800-3, "second
environment"
2)
.
Application in "first environment" possible with line filters.
Approval cULus (File No.: E192450), CE, RCM, EAC, KC
Ambient conditions During storage
3)
During transport
3)
During operation
Ambient temperature -25° … +55° C -25 ... +70 °C
from
–40 °C
for 24 hours
... +40° C
up to + 50° C with derating
Relative humidity
(no condensation)
Corresponds to class
5 to 95%
1K4 according to EN
60721-3-1
5 ... 95% at 40° C
2K3 according to
EN 60721-3-2
5 ... 95%
3K3 according to
EN 60721-3-3
Environmental class / harm‐
ful chemical substances
1C2 according to
EN 60721-3-1
2C2 according to
EN 60721-3-2
3C2 according to
EN 60721-3-3
Organic/biological influences 1B1 according to
EN 60721-3-1
2B1 according to
EN 60721-3-2
3B1 according to
EN 60721-3-3
Pollution degree 2 according to EN 61800-5-1
Installation altitude up to 1000 m above sea level without derating,
> 1000 m above sea level with derating (see Chapter Restrictions for special ambient condi‐
tions (Page 510))
Mechanical strength During storage
3)
During transport
3)
During operation
Vibrational load
- Displacement
- Acceleration
Fc test according to EN
60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g at 9 ... 200 Hz
Fc test according to EN
60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g at 9 ... 200 Hz
Fc test according to EN
60068-2-6
0.075 mm for 10 ... 58 Hz
9.81 ma/s² (1 x g) at > 58 ...
200 Hz
Shock load
- Displacement
- Acceleration
Fc test according to EN
60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g for 9 ... 200 Hz
Fc test according to EN
60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g for 9 ... 200 Hz
Test according to EN
60068-2-27 (EA shock type)
49 ma/s² (5 x g)/30 ms
147 m/s² (15 x g)/11 ms
Deviations from the defined classes are shown in
italics
.
1)
maximum sound pressure level, ascertained in the IP20 cabinet
2)
Standard construction: Devices installed in the control cabinet with installation in conformance with EMC regulations, line
reactor uk = 2%, shielded motor cable (e.g. Protoflex EMC) with max. 100 m cable length,
line harmonics according to EN 61000‑2‑4: Class 2, THD(U) total = 8% for typical line conditions (RSC > 30 ... 50); THD(I)
total: typically 30 … 45 % (15 < RSC < 50)
3)
in transport packaging
Technical data
10.5 Technical data, PM330 Power Module
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE 465