3. Remove the cable gland plate from the bottom of the inverter.
%ROWLQJSODWH
1P
&DEOHJODQGV
1P
5XEEHUVOHHYHV
Diameters of the drill holes in the cable gland plates:
20.5 mm Control cables
40.5 mm Mains and motor cables, FSD
50.5 mm Mains and motor cables, FSE
63.5 mm Mains and motor cables, FSF
Figure 4-16 Bolting plates for PM230 FSD … FSF Power Modules
4. Assemble the cable glands with the prepared cables and EMC cable glands for the control
cables.
5. Seal any unused bushings with a rubber sleeve.
6. Secure the bolting plate to the inverter enclosure. Tightening torque 2 Nm.
Make sure that the seal of the bolting plate is not damaged.
7. Connect the mains supply and the motor.
0DLQVVXSSO\0RWRU
8/
9/
:/
3(
8
9
:
Figure 4-17 Connections for PM230 Power Modules, FSD … FSF
8. Close the door of the Power Module.
Make sure that the door seal of the Power Module is not damaged.
Now you have connected both the mains supply and the motor to the FSD … FSF Power
Module.
Installing
4.4 Connecting the line supply and motor
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE 93