Communication according to PROFIdrive
3.4 Acyclic communication
Communication
Function Manual, 12/2018, 6SL3097-5BD00-0BP0
57
Error
value
Meaning
Remark
Additional
info
0x6C
Parameter %s [%s]: Unknown unit.
0x6D Parameter %s [%s]: Write access
only in the commissioning state,
encoder (p0010 = 4).
0x6E Parameter %s [%s]: Write access
only in the commissioning state,
motor (p0010 = 3).
0x6F Parameter %s [%s]: Write access
only in the commissioning state,
power unit (p0010 = 2).
0x70 Parameter %s [%s]: Write access
only in the quick commissioning
mode (p0010 = 1).
0x71 Parameter %s [%s]: Write access
only in the ready mode (p0010 = 0).
0x72 Parameter %s [%s]: Write access
only in the commissioning state,
parameter reset (p0010 = 30).
0x73 Parameter %s [%s]: Write access
only in the commissioning state,
Safety (p0010 = 95).
0x74 Parameter %s [%s]: Write access
only in the commissioning state, tech.
application/units (p0010 = 5).
0x75 Parameter %s [%s]: Write access
only in the commissioning state
(p0010 not equal to 0).
0x76 Parameter %s [%s]: Write access
only in the commissioning state,
download (p0010 = 29).
0x77 Parameter %s [%s] must not be writ-
ten during download.
0x78 Parameter %s [%s]: Write access
only in the commissioning state, drive
configuration (device: p0009 = 3).
0x79 Parameter %s [%s]: Write access
only in the commissioning state,
define drive type (device: p0009 = 2).
0x7A Parameter %s [%s]: Write access
only in the commissioning state, data
record base configuration (de-
vice: p0009 = 4).
0x7B Parameter %s [%s]: Write access
only in the commissioning state,
device configuration (de-
vice: p0009 = 1).