Communication according to PROFIdrive
3.4 Acyclic communication
Communication
58 Function Manual, 12/2018, 6SL3097-5BD00-0BP0
0x7C Parameter %s [%s]: Write access
only in the commissioning state,
device download (de-
– –
0x7D Parameter %s [%s]: Write access
only in the commissioning state,
device parameter reset (de-
– –
0x7E Parameter %s [%s]: Write access
only in the commissioning state,
device ready (device: p0009 = 0).
– –
0x7F Parameter %s [%s]: Write access
only in the commissioning state,
device (device: p0009 not equal to 0).
– –
0x81 Parameter %s [%s] must not be writ-
– –
0x82 Transfer of master control is blocked
– –
0x83
Parameter %s [%s]: Requested BICO
interconnection not possible.
BICO output does not supply float values. The BICO input,
however, requires a float value.
–
0x84 Parameter %s [%s]: Parameter
change inhibited
(refer to p0300, p0400, p0922)
– –
0x85 Parameter %s [%s]: Access method
not defined.
– –
0x87 Write job will not be executed. The write request is rejected because know-how protection
–
0xC8 Below currently valid limit. Modification request for a value that, although within "abso-
lute" limits, is below the currently valid lower limit.
–
0xC9 Above currently valid limit. Modification request for a value that, although within "abso-
lute" limits, is above the currently valid upper limit (e.g. gov-
erned by the current converter rating).
–
0xCC Write access not permitted.
Write access is not permitted because an access code is not
available.
–