Commissioning
5.4 Creating a project offline in Startdrive
76 Getting Started, 12/2018, 6SL3097-5AG30-0BP0
When first switched on with a new/modified network, an automatic controller setting must be
implemented using the line and DC link identification routine (p3410). While the identification
routine is running, it is not permissible for other loads to be switched in/switched out.
1. Select the infeed in the device view and open the Inspector window.
2. Select the "Line Module details > Line Module settings" menu in the Inspector window.
In the screen form, the following setting options are displayed:
Figure 5-10 Example: Detailed settings for infeed for ALM
3. In order to parameterize the device supply voltage, click the icon next to the "Line
data/operating mode" entry.
The "Line data/operating mode" screen form opens:
Figure 5-11 Example: Line data/operating mode for ALM