Additional system components
7.3 Sensor Module Cabinet-Mounted SMC30
SINAMICS DCM DC Converter
206 Operating Instructions, 12/2018, A5E34763375A
Sensor Module Cabinet-Mounted SMC30
Supported types
The SINAMICS DC MASTER only supports the Sensor Module Cabinet-Mounted SMC30
with article number 6SL3055-0AA00-5CA2. Other types may not be used. You can easily
identify whether the version is supported by the width of the module:
Table 7- 12 SMC30 types
Use with SINAMICS DC MASTER
6SL3055-0AA00-5CA0 50 mm Not possible
Number of SMC30s connected
The SINAMICS DC MASTER supports the connection of
Sensor Module Cabinet-
Mounted SMC30.
The Sensor Module Cabinet-Mounted SMC30 evaluates encoder signals and transmits the
speed, actual position value, and, if necessary, the motor temperature and reference point
via DRIVE-CLiQ to the Control Unit.
The SMC30 is used to evaluate encoder signals from encoders with TTL, HTL, or SSI
interfaces.
A combination of a TTL/HTL signal and SSI absolute signal is possible at terminals
X521/X531 if both signals are derived from the same measured variable.