Descriptions of functions
10.4 Communication via PROFIBUS DP
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
463
Device identification
Identification for individual slaves facilitates diagnostics and provides an overview of the
nodes on the PROFIBUS.
The information for each slave is stored in the following CU-specific parameter:
r0964[0...6] device identification
Bus terminating resistor and shielding
Reliable data transmission via PROFIBUS depends, amongst other things, on the setting of
the bus terminating resistors and the shielding of the PROFIBUS cables.
Bus terminating resistor
The bus terminating resistors in the PROFIBUS plugs must be set as follows:
First and last nodes in the line: Switch on terminating resistor
Other nodes in the line: Switch off terminating resistor
Shielding of the PROFIBUS cables
The cable shield must be connected in the plug through a large surface area at both
ends. See also Chapter "PROFIBUS connection (Page 455)".
10.4.3.3
Commissioning PROFIBUS
Preconditions and assumptions for commissioning
PROFIBUS slave
The PROFIBUS address to be set for the application is known.
The telegram type for each drive object is known by the application.
PROFIBUS master
The communication properties of the SINAMICS DCM slave must be available in the
master (GSD file or Drive ES slave OM).

Table of Contents

Other manuals for Siemens SINAMICS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS Series and is the answer not in the manual?

Siemens SINAMICS Series Specifications

General IconGeneral
Product LineSINAMICS
Cooling MethodAir-cooled, Liquid-cooled
Voltage Range200 V to 690 V
Power Range0.12kW - 250kW
Communication InterfacesPROFINET, PROFIBUS, Ethernet
Control ModesVector control, V/f control
Protection ClassIP20
TypeVariable Frequency Drives (VFD)

Related product manuals