Descriptions of functions
10.6 Communication via SINAMICS Link
SINAMICS DCM DC Converter
522 Operating Instructions, 12/2018, A5E34763375A
Figure 10-43 SINAMICS Link: Configuration example
10.6.5
Communication failure when booting or in cyclic operation
If at least one sender does not correctly boot after commissioning or fails in cyclic operation,
then alarm A50005 is output to the other nodes: "Sender was not found on SINAMICS Link".
The message contains the number of the faulted node. After you have resolved the fault at
the node involved and the system has identified the node, the system automatically
withdraws the alarm.
If several nodes are involved, the message occurs a multiple number of times consecutively
with different node numbers. After you have resolved all of the faults, the system
automatically withdraws the alarm.
When a node fails in cyclic operation, in addition to alarm A50005, fault F08501 is output:
"COMM BOARD: Monitoring time, process data expired"
At node 1, fault F08501 is not triggered. This node should be used for specifying setpoint
values to other nodes.

Table of Contents

Other manuals for Siemens SINAMICS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS Series and is the answer not in the manual?

Siemens SINAMICS Series Specifications

General IconGeneral
Product LineSINAMICS
Cooling MethodAir-cooled, Liquid-cooled
Voltage Range200 V to 690 V
Power Range0.12kW - 250kW
Communication InterfacesPROFINET, PROFIBUS, Ethernet
Control ModesVector control, V/f control
Protection ClassIP20
TypeVariable Frequency Drives (VFD)

Related product manuals