Descriptions of functions
10.4 Communication via PROFIBUS DP
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
481
10.4.4.4
GSD during operation
Generic station description file
In special generic station description files (GSD), the properties of a PROFIBUS slave are
uniquely and fully described to use PROFIBUS direct data exchange for SINAMICS.
The GSD files can be found:
On the Internet. For the link, see "Preface (Page 3)"
On the memory card in the directory \\SIEMENS\SINAMICS\DATA\CFG\
Universal module
Axis separator
Standard telegram1, PZD-2/2
Standard telegram20, PZD-2/6
SIEMENS telegram 220, PZD-10/10
SIEMENS telegram 352, PZD-6/6
Free telegram, PZD-4/4
Free telegram, PZD-8/8
Free telegram, PZD-16/16
Free telegram, PZD-32/32
Free telegram, PZD-64/64
Slave-to-slave, PZD-1
Slave-to-slave, PZD-2
Slave-to-slave, PZD-4
Slave-to-slave, PZD-8
The SINAMICS S DXB GSD file contains among other things standard telegrams, free
telegrams and slave-to-slave telegrams for configuring direct data exchange. The user must
take these telegram parts and an axis separator after each drive object to compose a
telegram for the drive unit.
Processing a GSD file in HW Config is covered in the SIMATIC documentation. Suppliers of
PROFIBUS components can provide their own bus configuration tool. The description of the
respective bus configuration tool is described in the relevant documentation.
Device identification
Identification for individual slaves facilitates diagnostics and provides an overview of the
nodes on the PROFIBUS.
The information for each slave is stored in the Control Unit parameter r0964[0...6] device
identification.

Table of Contents

Other manuals for Siemens SINAMICS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS Series and is the answer not in the manual?

Siemens SINAMICS Series Specifications

General IconGeneral
Product LineSINAMICS
Cooling MethodAir-cooled, Liquid-cooled
Voltage Range200 V to 690 V
Power Range0.12kW - 250kW
Communication InterfacesPROFINET, PROFIBUS, Ethernet
Control ModesVector control, V/f control
Protection ClassIP20
TypeVariable Frequency Drives (VFD)