Descriptions of functions
10.16 Technology controller
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
575
10.16
Technology controller
Features
Simple control functions can be implemented with the technology controller, e.g.:
Level control
Temperature control
Dancer position control
Pressure control
Flow control
Simple closed-loop controls without higher-level controller
Tension control
The technology controller features:
Two scalable setpoints
Scalable output signal
The output limits can be activated and deactivated via the ramp-function generator.
The D component can be switched into the control deviation or actual value channel.
Description
The technology controller is designed as a PID controller, whereby the differentiator can be
switched to the control deviation channel or the actual value channel (factory setting). The P,
I, and D components can be set separately. A value of 0 deactivates the corresponding
component. Setpoints can be specified via two connector inputs. The setpoints can be
scaled via parameters (p2255 and p2256). A ramp-function generator in the setpoint channel
can be used to set the setpoint ramp-up/ramp-down time via parameters p2257 and p2258.
The setpoint and actual value channel each have a smoothing element. The smoothing time
can be set via parameters p2261 and p2265.
Pre-control can be integrated via a connector input.
The output can be scaled via parameter p2295 and the control direction reversed. It can be
limited via parameters p2291 and p2292 and interconnected as required via a connector
output (r2294).
The actual value can be fed in, for example, via an analog input.
If a PID controller has to be used for control reasons, the D component is switched to the
setpoint/actual value difference (p2263 = 1) unlike in the factory setting. This is always
necessary when the D component is to be effective, even if the reference variable changes.
The D component can only be activated when p2274 > 0.

Table of Contents

Other manuals for Siemens SINAMICS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS Series and is the answer not in the manual?

Siemens SINAMICS Series Specifications

General IconGeneral
Product LineSINAMICS
Cooling MethodAir-cooled, Liquid-cooled
Voltage Range200 V to 690 V
Power Range0.12kW - 250kW
Communication InterfacesPROFINET, PROFIBUS, Ethernet
Control ModesVector control, V/f control
Protection ClassIP20
TypeVariable Frequency Drives (VFD)

Related product manuals