Operation
9.1 Basic information
SINAMICS DCM DC Converter
354 Operating Instructions, 12/2018, A5E34763375A
DDS: Drive data set
A drive data set contains various adjustable parameters that are relevant for open-loop and
closed-loop drive control:
Numbers of the assigned encoder data sets:
p0187 and p0188: Up to 2 assigned encoder data sets (EDS)
Various control parameters, e.g.:
Speed limits min./max. (p50512, p50513)
Characteristic data of ramp-function generator (p50295 ff)
Characteristic data of controller (p50540 ff)
...
The parameters that are grouped together in the drive data set are identified in the
SINAMICS DCM List Manual by "DDS" and are provided with index [0...n].
It is possible to parameterize several drive data sets. You can switch easily between different
drive configurations (control type, motor, encoder) by selecting the corresponding drive data
set.
A drive object can manage 4 drive data sets.
Binector inputs p0820 and p0821 are used to select a drive data set. They represent the
number of the drive data set (0 to 3) in binary format (where p0821 is the most significant
bit).
p0820 BI: Drive data set selection DDS, bit 0
p0821 BI: Drive data set selection DDS, bit 1
EDS: Encoder data set
An encoder data set contains various adjustable parameters for the connected encoder that
are relevant for configuring the drive.
Adjustable parameters, e.g.:
Encoder interface component number (p0141)
Encoder component number (p0142)
Encoder type selection (p0400)
The parameters that are grouped together in the encoder data set are identified in the
parameter list by "EDS" and are provided with index [0...n].
A separate encoder data set is required for each encoder controlled by the Control Unit. Up
to 2 encoder data sets are assigned to a drive data set via parameters p0187 and p0188.
It is only possible to switch an encoder data set by means of a DDS switchover. When a
drive data set is selected, the assigned encoder data sets are selected automatically.

Table of Contents

Other manuals for Siemens SINAMICS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS Series and is the answer not in the manual?

Siemens SINAMICS Series Specifications

General IconGeneral
Product LineSINAMICS
Cooling MethodAir-cooled, Liquid-cooled
Voltage Range200 V to 690 V
Power Range0.12kW - 250kW
Communication InterfacesPROFINET, PROFIBUS, Ethernet
Control ModesVector control, V/f control
Protection ClassIP20
TypeVariable Frequency Drives (VFD)

Related product manuals