EasyManuals Logo

Siemens SINAMICS Series User Manual

Siemens SINAMICS Series
758 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #416 background imageLoading...
Page #416 background image
Descriptions of functions
10.3 Communication according to PROFIdrive
SINAMICS DCM DC Converter
414 Operating Instructions, 12/2018, A5E34763375A
STW1 (control word 1)
See function diagram [2442].
Table 10- 8 Control word 1 (STW1)
Bit
Meaning
Explanation
Operating
condition
BICO
0 0 = OFF1 (OFF1) 0: Deceleration on the down ramp, then pulse
inhibit, line contactor (if present) is opened
1 BI: p0840
0 → 1 = ON
Pulse enable possible
1 0 = Coast down (OFF2) 0: Pulse inhibit, line contactor (if present) is
opened
1 BI: p0844
BI: p0845
1 = Do not coast down
Enable possible
Note: Control signal OFF2 is generated by ANDing BI: p0844 and BI: p0845.
2 0 = Quick stop (OFF3) 0: Deceleration on the quick stop ramp, then
pulse inhibit, line contactor (if present) is opened.
1 BI: p0848
1 = No quick stop
Enable possible
Note: Control signal OFF3 is generated by ANDing BI: p0848 and BI: p0849.
3 0 = Inhibit operation 0: Pulse inhibit. The motor coasts down. The
"Ready for Operation" state remains set.
1 BI: p0852
1 = Enable operation
1: Pulse enable, ramp-up with active setpoint
4 0 = Inhibit ramp-function
generator
0: The ramp-function generator output is set to
setpoint "0".
1 BI: p1140
1 = Enable ramp-function
generator
5 0 = Stop ramp-function
generator
0: The current setpoint is frozen at the ramp-
function generator output.
1 BI: p1141
1 = Start ramp-function
generator
6 1 = Enable speed setpoint 1: The speed setpoint at the input of the ramp-
function generator is enabled.
1 BI: p1142
0 = Inhibit speed setpoint 0: The speed setpoint at the input of the ramp-
function generator is set to zero. The drive
brakes in accordance with the set ramp-down
time.
7 0 → 1 = Acknowledge fault A positive edge change acknowledges all the
current faults.
- BI: p2103
Note: Acknowledgement is realized with a 0/1 edge via BI: p2103 or BI: p2104 or BI: p2105.
8
Reserved
-
-
9
Reserved
-
-
10 1 = Control via PLC 1: PROFIBUS control words and setpoints are
analyzed.
1 BI: p0854
0: PROFIBUS control words and setpoints are
not analyzed.
Note: This bit should not be set to "1" until the PROFIBUS slave has returned an appropriate status via ZSW1.9
= "1".

Table of Contents

Other manuals for Siemens SINAMICS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS Series and is the answer not in the manual?

Siemens SINAMICS Series Specifications

General IconGeneral
Product LineSINAMICS
Cooling MethodAir-cooled, Liquid-cooled
Voltage Range200 V to 690 V
Power Range0.12kW - 250kW
Communication InterfacesPROFINET, PROFIBUS, Ethernet
Control ModesVector control, V/f control
Protection ClassIP20
TypeVariable Frequency Drives (VFD)

Related product manuals