Maintenance
11.2 Replacing components
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
695
Replacing fans in 1200 A devices
1. Remove the front cover of the SINAMICS DC MASTER
2. Withdraw the fan connector
and the fan monitoring
3. Release the nuts
4. Remove the fan including the fan support strut
5. Install the new fan in the reverse sequence, tightening torque for the nuts
= 15 Nm
Figure 11-6 Replacing fans in 1200 A devices