Pickup logic and tripping logic
The pickup signals of the individual phases (or the ground) and of the stages are linked in such a way that
both the phase information and the stage which has picked up are output (Table 2-3).
Table 2-3 Pickup signals of the individual phases
Internal Indication Figure Output Indication No.
Ι>> Trip L1
Ι> Trip L1
Ιp Trip L1
Ι>>> Trip L1
Figure 2-16
Figure 2-17
Figure 2-19
O/C Pickup L1
7162
Ι>> Trip L2
Ι> Trip L2
Ιp Trip L2
Ι>>> Trip L2
Figure 2-16
Figure 2-17
Figure 2-19
O/C Pickup L2
7163
Ι>> Trip L3
Ι> Trip L3
Ιp Trip L3
Ι>>> Trip L3
Figure 2-16
Figure 2-17
Figure 2-19
O/C Pickup L3
7164
Ι>> Trip E
Ι> Trip E
Ιp TripE
Ι>>> Trip E
Figure 2-16
Figure 2-17
Figure 2-19
O/C Pickup E
7165
Ι>> Trip L1
Ι>> Trip L2
Ι>> Trip L3
Ι>> Trip E
Figure 2-16
Figure 2-16
Figure 2-16
Figure 2-16
O/C PICKUP I>>
7191
Ι> Trip L1
Ι> Trip L2
Ι> Trip L3
Ι> Trip E
O/C PICKUP I>
7192
Ιp Trip L1
Ιp Trip L2
Ιp Trip L3
Ιp Trip E
Figure 2-17
Figure 2-17
Figure 2-17
Figure 2-17
O/C PICKUP Ip
7193
Ι>>> Trip L1
Ι>>> Trip L2
Ι>>> Trip L3
Ι>>> Trip E
Figure 2-19
Figure 2-19
Figure 2-19
Figure 2-19
I-STUB PICKUP
7201
(All pickups)
O/C PICKUP
7161
For the tripping signals (Table 2-4) the stage which caused the tripping is also output. If the device has the
option to trip single-pole and if this option has been activated, the pole which has been tripped is also indi-
cated in case of single-pole tripping (refer also to Section 2.8.1 Function Control “Tripping Logic of the Entire
Device”).
Functions
2.3 Overcurrent protection (optional)
74 SIPROTEC 4, 7VK61, Manual