[td_io240x, 3, en_US]
Figure 3-70
IO240 – Connection Diagram
Connections of GIS-LPIT Sensors
When connecting the Siemens Energy GIS-LPIT sensors to the LPIT module IO240, proceed as follows:
²
Use the delivered cable LEONI L45551-P42-B5 and confection the cable as explained in the user manual
of the LPIT GIS sensor.
The L45551-P42-B5 cable has 4 twisted pairs: 1 pair for the low-power voltages, 1 pair for the low-power
currents, and 2 pairs for the PT100 temperature sensor connection. Each conductor is terminated with a
wire ferrule (length = 12 mm, wire gauge = 0.5 mm2). Each internal shield is connected with a cable
ring-type lug (for M4 screw).
3.2.20.3
Electronic Modules
3.2 Input and Output Modules of the Modular Devices
116 SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-M, Edition 12.2021