2 Functions
122
7SA522 Manual
C53000-G1176-C155-3
2.4.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
2.4.4 Information List
Addr. Parameter Setting Options Default Setting Comments
4501 STATE PROT I 1 ON
OFF
ON State of protection interface 1
4502 CONNEC. 1 OVER F.optic direct
Com conv 64 kB
Com conv 128 kB
Com conv 512 kB
F.optic direct Connection 1 over
4505A PROT 1 T-DELAY 0.1 .. 30.0 ms 30.0 ms Prot 1: Maximal permissible delay
time
4509 T-DATA DISTURB 0.05 .. 2.00 sec 0.10 sec Time delay for data disturbance
alarm
4510 T-DATAFAIL 0.0 .. 60.0 sec 6.0 sec Time del for transmission failure
alarm
4511 Td ResetRemote 0.00 .. 300.00 sec; ∞ 0.00 sec Remote signal RESET DELAY for
comm.fail
4601 STATE PROT I 2 ON
OFF
ON State of protection interface 2
4602 CONNEC. 2 OVER F.optic direct
Com conv 64 kB
Com conv 128 kB
Com conv 512 kB
F.optic direct Connection 2 over
4605A PROT 2 T-DELAY 0.1 .. 30.0 ms 30.0 ms Prot 2: Maximal permissible delay
time
4701 ID OF RELAY 1 1 .. 65534 1 Identification number of relay 1
4702 ID OF RELAY 2 1 .. 65534 2 Identification number of relay 2
4703 ID OF RELAY 3 1 .. 65534 3 Identification number of relay 3
4710 LOCAL RELAY relay 1
relay 2
relay 3
relay 1 Local relay is
No. Information Type of In-
formation
Comments
3196 local Teststate IntSP Local relay in Teststate
3215 Wrong Firmware OUT Incompatible Firmware Versions
3217 PI1 Data reflec OUT Prot Int 1: Own Datas received
3218 PI2 Data reflec OUT Prot Int 2: Own Datas received
3227 >PI1 light off SP >Prot Int 1: Transmitter is switched off
3228 >PI2 light off SP >Prot Int 2: Transmitter is switched off
3229 PI1 Data fault OUT Prot Int 1: Reception of faulty data