4.19 Monitoring Function
477
7SA522 Manual
C53000-G1176-C155-3
4.19 Monitoring Function
Measured Values
Current sum I
F
= | I
L1
+ I
L2
+ I
L3
+ k
I
· I
E
| >
SUM.I Threshold · I
N
+ SUM.I factor ·Σ | I |
- SUM I THRESHOLD for I
N
= 1 A 0.05 A to 2.00 A Increments 0.01 A
for I
N
= 5 A 0.25 A to 10.00 A Increments 0.01 A
- SUM.I factor 0.00 to 0.95 Increments 0.01
Voltage sum U
F
= | U
L1
+ U
L2
+ U
L3
+ k
U
· U
EN
| > 25 V
Current symmetry | I
min
| / | I
max
| < BAL.FACTOR.I
as long as I
max
/ I
N
> BAL.I LIMIT / I
N
- BAL.FACTOR I 0.10 to 0.95 Increments 0.01
- BAL.I LIMIT for I
N
= 1 A 0.10 A to 1.00 A Increments 0.01 A
for I
N
= 5 A 0.50 A to 5.00 A Increments 0.01 A
- T BAL.I LIMIT 5 s to 100 s Increments 1 s
Broken conductor One conductor without current, the others with current
Voltage symmetry | U
min
| / | U
max
| < BAL.FACTOR.U
as long as| U
max
| > BAL.U LIMIT
- BAL.FACTOR U 0.58 to 0.95 Increments 0.01
- BAL.U LIMIT 10 V to 100 V Increments 1 V
- T BAL.U LIMIT 5 s to 100 s Increments 1 s
Voltage phase sequence U
L1
beforeU
L2
beforeU
L3
as long as | U
L1
|, | U
L2
| , | U
L3
| > 40 V/√3
Non-symmetrical voltages
(Fuse failure monitoring)
3 · U
0
> FFM U> OR 3 · U
2
> FFM U>
AND at the same time
3 · I
0
< FFM I< AND 3 · I
2
< FFM I<
- FFM U> 10 V to 100 V Increments 1 V
- FFM I< for I
N
= 1 A 0.10 A to 1.00 A Increments 0.01 A
for I
N
= 5 A 0.50 A to 5.00 A Increments 0.01 A
Three-phase measuring voltage failure
(fuse failure monitoring)
All U
Ph-E
< FFM UMEAS<
AND at the same time
All ∆I
Ph
< FFM Idelta
AND
All I
Ph
> (I
Ph
> (Dist.))
OR
All U
Ph-E
< FFM UMEAS<
AND at the same time
All I
Ph
< (I
Ph
> (Dist.))
AND
All I
Ph
> 40 mA
- FFM U<max 2 V to 100 V Increments 1 V
- FFM I
delta
for I
N
= 1 A 0.05 A to 1.00 A Increments 0.01 A
for I
N
= 5 A 0.25 A to 5.00 A Increments 0.01 A
- T V-Supervision (wait time for additional measured
voltage failure monitoring)
0.00 s to 30.00 s Increments 0.01 s
- T VT mcb 0 ms to 30 ms Increments 1 ms