EasyManuals Logo

Siemens siprotec 7SA522 User Manual

Siemens siprotec 7SA522
606 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #337 background imageLoading...
Page #337 background image
2.20 Function control and circuit breaker testing
337
7SA522 Manual
C53000-G1176-C155-3
Single-pole Dead
Time
During a single-pole dead time, the load current flowing in the two healthy phases
forces a current flow via earth which may cause undesired pickup. The temporarily ap-
plying zero-sequence voltage may also prompt undesired responses of the protection
functions.
The messages ´SROHRSHQ/µ (FNo. 591), ´SROHRSHQ/µ (FNo. 592) and
´SROHRSHQ/µ (FNo. 593) are generated in addition if the “Open Pole Detector
recognizes that current and voltage are absent in one phase – but neither in the other
phases current is flowing. In this case, the message will be held up only for as long as
the condition is fulfilled. This enables a single-pole automatic reclosure to be detected
on an unloaded line.
2.20.1.4 Pickup Logic for the Entire Device
Phase Segregated
Fault Detection
The fault detection logic combines the fault detection (pick-up) signals of all protection
functions. In the case of those protection functions that allow for phase segregated
pick-up, the pick-up is output in a phase segregated manner. If a protection function
detects an earth fault, this is also output as a common device alarm. Thus the alarms
´5HOD\3,&.83/µ, ´5HOD\3,&.83/µ, ´5HOD\3,&.83/µ and ´5HOD\
3,&.83(µ are available.
The annunciations above can be allocated to LEDs or output relays. For the local
display of fault event messages and for the transmission of event messages to a per-
sonal computer or a centralized control system, several protection functions provide
the faulted phase information in a single message, e.g. ´'LV3LFNXS/(µ for the
distance protection fault detection in L1–L2–E only one such message appears. It rep-
resents the complete definition of the fault detection.
General Pickup The pickup signals are combined with OR and lead to a general pickup of the device.
It is signaled with the alarm ´5HOD\3,&.83µ. If no protection function of the device
has picked up any longer, ´5HOD\3,&.83µ disappears (message: “OFF”).
General device pickup is a precondition for a series of internal and external functions
that occur subsequently. The following are among the internal functions controlled by
general device pickup:
Opening of fault case: From general device pickup to general device drop out, all
fault messages are entered in the trip log.
Initialization of fault storage: The storage and maintenance of fault values can also
be made dependent on the occurrence of a trip command.
Generation of Spontaneous annunciations: Certain fault messages can be dis-
played as so called spontaneous messages (see “Spontaneous Indications” below).
These display messages can also be made dependent on the general device trip.
Start action time of automatic reclosure (if available and used)
External functions may be controlled by this indication via an output contact. Examples
are:
Automatic reclose devices,
Channel boost in conjunction with signal transmission by PLC,
Further additional devices or similar.

Table of Contents

Other manuals for Siemens siprotec 7SA522

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA522 and is the answer not in the manual?

Siemens siprotec 7SA522 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA522
CategoryProtection Device
LanguageEnglish

Related product manuals