2.22 Command processing
363
7SA522 Manual
C53000-G1176-C155-3
Acknowledgment and resetting commands for setting and resetting internal buffers
or data stocks.
Information status commands to set/delete the additional “Information Status” item
of a process object, such as
Acquisition blocking,
Output blocking.
2.22.1.2 Sequence in the Command Path
Security mechanisms in the command path ensure that a switch command can be
carried out only if the test of previously established criteria has been successfully com-
pleted. Additionally, user-defined interlocking conditions can be configured separately
for each device. The actual execution of the command is also monitored after its re-
lease. The entire sequence of a command is described briefly in the following.
Checking a
Command
Please observe the following:
Command entry (e.g. using the keypad on the local user interface of the device)
Check password access rights;
Check switching mode (interlocking activated/deactivated) selection of deac-
tivated interlocking status.
User configurable interlocking checks:
Switching authority,
Device position check (set vs. actual comparison);
Zone controlled / bay interlocking (logic using CFC);
System interlocking (centrally via SICAM);
Double operation (interlocking against parallel switching operation);
Protection blocking (blocking of switching operations by protective functions);
Check (synchronism check before a close command).
Fixed commands:
Internal process time (software watch dog which checks the time for processing
the control action between initiation of the control and final close of the relay con-
tact);
Configuration in process (if setting modification is in process, commands are re-
jected or delayed);
Equipment not present at output (if controllable equipment is not assigned to a
binary output, then the command is denied);
Output block (if an output block has been programmed for the circuit breaker, and
is active at the moment the command is processed, then the command is de-
nied);
Component hardware malfunction;

Table of Contents

Other manuals for Siemens siprotec 7SA522

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA522 and is the answer not in the manual?

Siemens siprotec 7SA522 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA522
CategoryProtection Device
LanguageEnglish

Related product manuals