EasyManuals Logo

Siemens siprotec 7SA522 User Manual

Siemens siprotec 7SA522
606 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #364 background imageLoading...
Page #364 background image
2 Functions
364
7SA522 Manual
C53000-G1176-C155-3
Command in progress (only one command can be processed at a time for each
circuit breaker or switch);
1–of–n check (for multiple allocations such as common contact relays it is
checked if a command procedure was already initiated for the output relays con-
cerned).
Command Execu-
t i o n M o n i t o r i n g
The following is monitored:
Interruption of a command because of a cancel command,
Running Time Monitor (feedback message monitoring time)
2.22.1.3 Switchgear Interlocking
Interlocking can be executed by the user-defined logic (CFC). System interlocking
checks in a SICAM
®
/SIPROTEC
®
system are usually categorized as follows:
System interlocking checked by a central control system (for interbay interlocking),
Zone controlled/bay interlocking checked in the bay device (for the feeder).
Zone Controlled/Bay Interlocking Zone controlled/bay interlocking relies on the object
data base (feedbacks) of the bay unit (here the SIPROTEC
®
4 relay) as was deter-
mined during configuration (see SIPROTEC
®
4 System Description).
The extent of the interlocking checks is determined by the configuration and interlock-
ing logic of the relay.
Switching objects that require system interlocking in a central control system are as-
signed to a specific parameter inside the bay unit (via configuration matrix).
For all commands, operation with interlocking (normal mode) or without interlocking
(test mode) can be selected:
for local commands by reprogramming the settings with password check,
for automatic commands, via command processing by CFC and Deactivated Inter-
locking Recognition,
for local / remote commands, using an additional interlocking disable command, via
Profibus.
Interlocked/
de-interlocked
Switching
The configurable command checks in the SIPROTEC
®
4 devices are also called “stan-
dard interlocking”. These checks can be activated via DIGSI
®
(interlocked switching /
tagging) or deactivated (non-interlocked).
De-interlocked or non-interlocked switching means that the configured interlock con-
ditions are not tested.
Interlocked switching means that all configured interlocking conditions are checked
within the command processing. If a condition could not be fulfilled, the command will
be rejected by a message with a minus added to it (e.g. “CO–”), followed by an oper-
ation response information. The rejection takes also place if a synchronism check is
carried out before closing and the conditions for synchronism are not fulfilled. Table 2-
17 shows the types of possible commands to switchgear, and the associated annun-
ciations. Indications designated with *) are displayed in the represented form in the
device display in the event logs and in DIGSI
®
on the other hand, they appear in spon-
taneous indications.

Table of Contents

Other manuals for Siemens siprotec 7SA522

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA522 and is the answer not in the manual?

Siemens siprotec 7SA522 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA522
CategoryProtection Device
LanguageEnglish

Related product manuals