4.3 Power Swing Detection (optional)
447
7SA522 Manual
C53000-G1176-C155-3
4.3 Power Swing Detection (optional)
Power swing detection Rate of the impedance vector and observation of the path
curve
Maximum power swing frequency Approx. 7 Hz
Power swing blocking programs Block 1st zone only
Block higher zones
Block 1st and 2nd zone
Block all zones
Power swing trip Trip following instable power swings
(out-of-step)
Trip time delay after power swing block 0.08 to 5.00 s Increments 0.01 s