Alternatively, check of the de-energized state before reclosing
Closing at asynchronous system conditions with prediction of the synchronization
time
Settable minimum and maximum voltage
Verification of the synchronous conditions or de-energized state also possible
before the manual closing of the circuit breaker, with separate limit values
Also measurement via transformer
Measuring voltages optionally phase-phase or phase-earth
Voltage Protection
(optional)
Overvoltage and undervoltage detection with different stages
Two overvoltage stages for the phase-earth voltages, with common time delay
Two overvoltage stages for the phase-phase voltages, with common time delay
Two overvoltage stages for the positive sequence voltage, with a time delay each,
optionally with compounding
Two overvoltage stages for the negative sequence voltage, with a time delay each
Two overvoltage stages for the zero sequence voltage or any other single-phase
voltage, with a time delay each
Settable drop-off to pick-up ratios for the overvoltage protection functions
Two undervoltage stages for the phase-earth voltages, with common time delay
Two undervoltage stages for the phase-phase voltages, with common time delay
Two undervoltage stages for the positive sequence voltage, with a time delay each
Settable current criterion for undervoltage protection functions
Frequency Protec-
tion (optional)
Monitoring on underfrequency (f<) and/or overfrequency (f>) with 4 frequency limits
and delay times that are independently adjustable
Very insensitive to phase angle changes
Large frequency range (approx. 25 Hz to 70 Hz)
Fault Location Initiated by trip command or reset of the pickup
Computation of the distance to fault with dedicated measured value registers
Fault location output in ohm, kilometers or miles and % of line length
Parallel line compensation can be selected
Taking into consideration the load current in case of single-phase earth faults fed
from both sides (settable)
Circuit Breaker
Failure Protection
(optional)
With definite time current stages for monitoring current flow through every pole of
the circuit breaker
With definite time monitoring time steps for single-pole and three-pole tripping
Start by trip command of every internal protection function
Start by external trip functions possible
Single-stage or two-stage