2.20 Function control and circuit breaker testing
339
7SA522 Manual
C53000-G1176-C155-3
These alarms can be allocated to LEDs or output relays. In the event of three-pole trip-
ping all three alarms pick up.
If single-pole tripping is possible, the protection functions generates a group signal for
the local displaying of alarms and for the transmission of the alarms to a PC or a
central control system, e.g. ´'LV7ULSS/µ, ´'LV7ULSS/µ, for single-pole
tripping by the distance protection and ´'LV7ULSSµ for three-pole tripping. Only
one of these alarms is displayed at a time. These alarms are also intended for the trip
command output to the circuit breaker.
Single-pole Trip-
ping after Two-
Phase Fault
Single-pole tripping for two-phase faults is a special feature. If a phase-phase fault
without earth
occurs in an earthed system, this fault can be cleared by single-pole trip
and automatic reclosure in one of the faulted phases, as the short-circuit path is inter-
rupted in this manner. The phase selected for tripping must be the same at both line
ends (and should be the same for the entire system).
The setting parameter 7ULSSK)OW (address ) allows to select whether this trip-
ping should be SROHOHDGLQJ, i.e. single-pole tripping of the leading phase, or
SROHODJJLQJ, i.e. single-pole tripping of the lagging phase. Standard setting is
SROH, i.e. three-pole tripping after two-phase faults (default setting).
Table 2-12 One-pole and three-pole trip depending on fault type
Type of Fault
(from Protection Func-
tion)
Parameter
Trip2phFlt
Output signals for trip
TRIP 1p. L1 TRIP 1p. L2 TRIP 1p. L3 Relay TRIP
3ph.
L1 (any) X
L2 (any) X
L3 (any) X
L1 E (any) X
L2 E (any) X
L3 E (any) X
L1 L2 3pole X
L1 L2 1pole leading Ø X
L1 L2 1pole lagging Ø X
L2 L3 3pole X
L2 L3 1pole leading Ø X
L2 L3 1pole lagging Ø X
L1 L3 3pole X
L1 L3 1pole leading Ø X
L1 L3 1pole lagging Ø X
L1 L2 E (any) X
L2 L3 E (any) X
L1 L3 E (any) X
L1 L2 L3 (any) X
L1 L2 L3 E (any) X
E(any) X