EasyManuals Logo

Siemens siprotec 7SA522 User Manual

Siemens siprotec 7SA522
606 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #400 background imageLoading...
Page #400 background image
3 Mounting and Commissioning
400
7SA522 Manual
C53000-G1176-C155-3
Is the polarity for current input I
4
correct (if used)?
Is the polarity for voltage input U
4
correct (if used, e.g. for broken delta winding
or busbar voltage)?
Check the functions of all test switches that are installed for the purposes of sec-
ondary testing and isolation of the device. Of particular importance are test switches
in current transformer circuits. Be sure these switches short-circuit the current
transformers when they are in the “test mode”.
The short-circuit feature of the current circuits of the device are to be checked. This
may be performed with an ohmmeter or other test equipment for checking continu-
ity. Make sure that terminal continuity is not wrongly simulated in reverse direction
via current transformers or their short circuit links.
Remove the front panel of the device (see also Figures 3-3 to 3-4).
Remove the ribbon cable connected to the input/output board with the measured
current inputs (on the front side it is the right PCB, for housing size
1
/
2
see Figure
3-3 slot 33, for housing size
1
/
1
see Figure 3-4 slot 33 right). Furthermore, remove
the PCB so that there is no more contact anymore with the plug-in terminal.
At the terminals of the device, check continuity for each pair of terminals that re-
ceives current from the CTs.
Firmly re-insert the I/O board. Carefully connect the ribbon cable. Be careful that
no connector pins are bent! Don't apply force!
At the terminals of the device, again check continuity for each pair of terminals
that receives current from the CTs.
Attach the front panel and tighten the screws.
Connect an ammeter in the supply circuit of the power supply. A range of about 2.5
A to 5 A for the meter is appropriate.
Switch on m.c.b. for auxiliary voltage (supply protection), check the voltage level
and, if applicable, the polarity of the voltage at the device terminals or at the con-
nection modules.
The measured steady-state current should correspond to the quiescent power con-
sumption of the device. Transient movement of the ammeter merely indicates the
charging current of capacitors.
Remove the voltage from the power supply by opening the protective switches.
Disconnect the measuring test equipment; restore the normal power supply con-
nections.
Apply voltage to the power supply.
Close the protective switches for the voltage transformers.
Verify that the voltage phase rotation at the device terminals is correct.
Switch off the miniature circuit breakers for the transformer voltage (VT mcb) and
the power supply.
Check tripping circuits to the circuit breakers.
Check the close circuits to the power system circuit breakers
Verify that the control wiring to and from other devices is correct.
Check the signalling connections.
Close the protective switches.

Table of Contents

Other manuals for Siemens siprotec 7SA522

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA522 and is the answer not in the manual?

Siemens siprotec 7SA522 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA522
CategoryProtection Device
LanguageEnglish

Related product manuals