3.3 Commissioning
417
7SA522 Manual
C53000-G1176-C155-3
Figure 3-24 Measuring voltages for the synchronism check
If not, first check whether one of the before named messages 2947 ´6\QF
8GLII!µ or 2949 ´6\QFϕGLII!µ is available in the spontaneous messages.
The message ´6\QF8GLII!µ indicates that the magnitude (ratio) adaptation is
incorrect. Check address  8OLQH8V\QF and recalculate the adaptation
factor, if necessary.
The message ´6\QFϕGLII!µ indicates that the phase relation of the busbar
voltage does not match the setting under address  8V\QFFRQQHFW (see
Section 2.1.3.1). When measuring across a transformer, address  ϕ8V\QF
8OLQH must also be checked; this must adapt the vector group (see Subsection
2.1.3.1). If these are correct, there is probably a reverse polarity of the voltage
transformer terminals for Usync.
The program 8V\QF8OLQH! = <(6 (Address ) and 6<1&&+(&. = <(6
(Address ) is set for synchronism check.
Open the VT mcb of the busbar voltage.
Via binary input (FNo.2906 ´!6\QF6WDUW$5µ ) initiate the measuring request.
There is no close release. If there is, the VT mcb for the busbar voltage is not allo-
cated. Check whether this is the required state, alternatively check the binary input
´!)$,/%XV97µ (FNo. 362).
The VT mcb of the busbar voltage is to be closed again.
Open the circuit breaker.
The program 8V\QF!8OLQH = <(6 (Address ) and 8V\QF!8OLQH =
12 (Address ) is set for synchronism check.
Via binary input (FNo. 2906´!6\QF6WDUW$5µ) initiate the measuring request.
The synchronism check must release closing (message ´6\QFUHOHDVHµ, FNo.
2951). Otherwise check all voltage connections and the corresponding parameters
again carefully as described in Section 2.1.3.1.
Open the VT mcb of the feeder voltage.
Via binary input (FNo.2906 ´!6\QF6WDUW$5µ ) initiate the measuring request.
No close release is given.
Open the VT mcb of the feeder voltage again.
Addresses  to  must be restored as they were changed for the test. If the
allocation of the LEDs or signal relays was changed for the test, this must also be re-
stored.

Table of Contents

Other manuals for Siemens siprotec 7SA522

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA522 and is the answer not in the manual?

Siemens siprotec 7SA522 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA522
CategoryProtection Device
LanguageEnglish

Related product manuals