4 Technical Data
436
7SA522 Manual
C53000-G1176-C155-3
System Interface (optional)
RS232
Transmission distance 15 m / 50 feet
RS485
Transmission distance 1 km / 3280 feet / 0.62 miles
Fibre optics (FO)
FO connector type ST connector
Connection for panel flush mounting
housing
Rear panel, mounting location “C”
Connection for panel surface mounting
housing
In console housing at device bottom
Optical wavelength λ = 820 nm
Laser Class I according to EN 60825-1/-2 Using glass fibre 50/125 µm or
For use of FO 62.5/125 µm
Permissible optical signal attenuation Max. 8 dB, with glass fibre 62.5/125 µm
Transmission distance Max. 1.5 km
Character idle state Selectable: factory setting “Light off”
RS232/RS485/Optical fibre/
Profibus RS485 / Profibus
optical fibre
DNP3.0/RS485
DNP3.0/Optical Fibre
Acc. to ordered version
Isolated interface for data transfer to a control terminal
RS232
Connection for panel flush mounting
housing
Rear panel, mounting location “B”,
9-pin D-subminiature female connector
Connection for panel surface mounting
housing
Up to /DD At the terminal on the case bottom
/EE and higher In console housing at case bottom
9-pin D-subminiature female connector
Test voltage 500 V; 50 Hz
Transmission speed Min. 4800 Baud; max. 38400 Baud
Factory setting 19200 Baud
Transmission distance Max. 15 m
RS485
Connection for panel flush mounting
housing
Rear panel, mounting location “B”,
9-pin D-subminiature female connector
Connection for panel surface mounting
housing
Up to /DD At the terminal on the case bottom
/EE and higher In console housing at case bottom
9-pin D-subminiature female connector
Test voltage 500 V; 50 Hz
Transmission speed Min. 4800 Bd, max. 38400 Bd
Factory setting 19200 Bd
Transmission distance Max. 1 km