A Appendix
524
7SA522 Manual
C53000-G1176-C155-3
the input indication “CB wait” is OFF and
the input indication “Door open” is OFF.
The disconnector can only be closed, if:
the circuit breaker is set to OPEN and
the earth switch is set to OPEN and
the disconnector is set to OPEN or CLOSE and
the input indication “Door open” is OFF.
The disconnector can only be closed, if:
the circuit breaker is set to OPEN and
the disconnector is set to OPEN or CLOSE and
the earth switch is set to OPEN or CLOSE and
the input indication “Door open” is OFF.
The earth switch can only be closed, if:
the circuit breaker is set to OPEN and
the disconnector is set to OPEN and
the earth switch is set to OPEN or CLOSE and
the input indication “Door open” is OFF.
If the above requirements are not fulfilled, the actions of the switch commands will be
blocked with error messages by DIGSI
®
.