A.7 Settings
531
7SA522 Manual
C53000-G1176-C155-3
411 PRE. TRIG. TIME Osc. Fault Rec. 0.05 .. 0.50 sec 0.25 sec Captured Waveform Prior to
Trigger
412 POST REC. TIME Osc. Fault Rec. 0.05 .. 0.50 sec 0.10 sec Captured Waveform after Event
415 BinIn CAPT.TIME Osc. Fault Rec. 0.10 .. 5.00 sec; ∞ 0.50 sec Capture Time via Binary Input
610 FltDisp.LED/LCD Device Target on PU
Target on TRIP
Target on PU Fault Display on LED / LCD
615 Spont. FltDisp. Device NO
YES
NO Spontaneous display of flt.annunci-
ations
640 Start image DD Device image 1
image 2
image 3
image 4
image 5
image 1 Start image Default Display
1103 FullScaleVolt. P.System Data 2 1.0 .. 1200.0 kV 400.0 kV Measurement: Full Scale Voltage
(100%)
1104 FullScaleCurr. P.System Data 2 10 .. 5000 A 1000 A Measurement: Full Scale Current
(100%)
1105 Line Angle P.System Data 2 30 .. 89 ° 85 ° Line Angle
1107 P,Q sign P.System Data 2 not reversed
reversed
not reversed P,Q operational measured values
sign
1110 x' P.System Data 2 1A 0.0050 .. 9.5000 Ω/km 0.1500 Ω/km x' - Line Reactance per length unit
5A 0.0010 .. 1.9000 Ω/km 0.0300 Ω/km
1111 Line Length P.System Data 2 0.1 .. 1000.0 km 100.0 km Line Length
1112 x' P.System Data 2 1A 0.0050 .. 15.0000 Ω/mi 0.2420 Ω/mi x' - Line Reactance per length unit
5A 0.0010 .. 3.0000 Ω/mi 0.0484 Ω/mi
1113 Line Length P.System Data 2 0.1 .. 650.0 Miles 62.1 Miles Line Length
1114 c' P.System Data 2 1A 0.000 .. 100.000 µF/km 0.010 µF/km c' - capacit. per unit line len. µF/km
5A 0.000 .. 500.000 µF/km 0.050 µF/km
1115 c' P.System Data 2 1A 0.000 .. 160.000 µF/mi 0.016 µF/mi c' - capacit. per unit line len.
µF/mile
5A 0.000 .. 800.000 µF/mi 0.080 µF/mi
1116 RE/RL(Z1) P.System Data 2 -0.33 .. 7.00 1.00 Zero seq. comp. factor RE/RL for
Z1
1117 XE/XL(Z1) P.System Data 2 -0.33 .. 7.00 1.00 Zero seq. comp. factor XE/XL for
Z1
1118 RE/RL(Z1B...Z5) P.System Data 2 -0.33 .. 7.00 1.00 Zero seq. comp.factor RE/RL for
Z1B...Z5
1119 XE/XL(Z1B...Z5) P.System Data 2 -0.33 .. 7.00 1.00 Zero seq. comp.factor XE/XL for
Z1B...Z5
1120 K0 (Z1) P.System Data 2 0.000 .. 4.000 1.000 Zero seq. comp. factor K0 for zone
Z1
1121 Angle K0(Z1) P.System Data 2 -135.00 .. 135.00 ° 0.00 ° Zero seq. comp. angle for zone Z1
1122 K0 (> Z1) P.System Data 2 0.000 .. 4.000 1.000 Zero seq.comp.factor K0,higher
zones >Z1
1123 AngleI K0(> Z1) P.System Data 2 -135.00 .. 135.00 ° 0.00 ° Zero seq. comp. angle, higher
zones >Z1
1126 RM/RL ParalLine P.System Data 2 0.00 .. 8.00 0.00 Mutual Parallel Line comp. ratio
RM/RL
1127 XM/XL ParalLine P.System Data 2 0.00 .. 8.00 0.00 Mutual Parallel Line comp. ratio
XM/XL
1128 RATIO Par. Comp P.System Data 2 50 .. 95 % 85 % Neutral current RATIO Parallel
Line Comp
1130A PoleOpenCurrent P.System Data 2 1A 0.05 .. 1.00 A 0.10 A Pole Open Current Threshold
5A 0.25 .. 5.00 A 0.50 A
1131A PoleOpenVoltage P.System Data 2 2 .. 70 V 30 V Pole Open Voltage Threshold
1132A SI Time all Cl. P.System Data 2 0.01 .. 30.00 sec 0.05 sec Seal-in Time after ALL closures
1134 Line Closure P.System Data 2 only with ManCl
I OR U or ManCl
CB OR I or M/C
I or Man.Close
only with ManCl Recognition of Line Closures with
1135 Reset Trip CMD P.System Data 2 CurrentOpenPole
Current AND CB
CurrentOpenPole RESET of Trip Command
Addr. Parameter Function C Setting Options Default Setting Comments