A Appendix
562
7SA522 Manual
C53000-G1176-C155-3
2845 AR 2nd cycle running (AR
2ndCyc. run.)
Autoreclosure OUT * ON * LED BO 40 157 2 Yes
2846 AR 3rd cycle running (AR
3rdCyc. run.)
Autoreclosure OUT * ON * LED BO 40 158 2 Yes
2847 AR 4th or higher cycle running
(AR 4thCyc. run.)
Autoreclosure OUT * ON * LED BO 40 159 2 Yes
2848 AR cycle is running in ADT mode
(AR ADT run.)
Autoreclosure OUT * ON * LED BO 40 130 2 Yes
2851 AR: Close command (AR
CLOSE Cmd.)
Autoreclosure OUT * ON m LED BO 128 128 1 No
2852 AR: Close command after 1pole,
1st cycle (AR Close1.Cyc1p)
Autoreclosure OUT * * * LED BO 40 152 1 No
2853 AR: Close command after 3pole,
1st cycle (AR Close1.Cyc3p)
Autoreclosure OUT * * * LED BO 40 153 1 No
2854 AR: Close command 2nd cycle
(and higher) (AR Close 2.Cyc)
Autoreclosure OUT * * * LED BO 128 129 1 No
2861 AR: Reclaim time is running (AR
T-Recl. run.)
Autoreclosure OUT * * * LED BO 40 161 1 No
2862 AR successful (AR successful) Autoreclosure OUT * * * LED BO 40 162 1 No
2864 AR: 1pole trip permitted by inter-
nal AR (AR 1p Trip Perm)
Autoreclosure OUT * * * LED BO 40 164 1 Yes
2865 AR: Synchro-check request (AR
Sync.Request)
Autoreclosure OUT * * * LED BO 40 165 2 Yes
2871 AR: TRIP command 3pole (AR
TRIP 3pole)
Autoreclosure OUT * ON * LED BO 40 171 2 Yes
2889 AR 1st cycle zone extension
release (AR 1.CycZoneRel)
Autoreclosure OUT * * * LED BO 40 160 1 No
2890 AR 2nd cycle zone extension
release (AR 2.CycZoneRel)
Autoreclosure OUT * * * LED BO 40 169 1 No
2891 AR 3rd cycle zone extension
release (AR 3.CycZoneRel)
Autoreclosure OUT * * * LED BO 40 170 1 No
2892 AR 4th cycle zone extension
release (AR 4.CycZoneRel)
Autoreclosure OUT * * * LED BO 40 172 1 No
2893 AR zone extension (general) (AR
Zone Release)
Autoreclosure OUT * * * LED BO 40 173 1 Yes
2894 AR Remote close signal send
(AR Remote Close)
Autoreclosure OUT * ON * LED BO 40 129 1 No
2895 No. of 1st AR-cycle CLOSE com-
mands,1pole (AR #Close1./1p=)
Statistics OUT
2896 No. of 1st AR-cycle CLOSE com-
mands,3pole (AR #Close1./3p=)
Statistics OUT
2897 No. of higher AR-cycle CLOSE
commands,1p (AR
#Close2./1p=)
Statistics OUT
2898 No. of higher AR-cycle CLOSE
commands,3p (AR
#Close2./3p=)
Statistics OUT
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Inputs
Function Key
Relay
Chatter suppression
Type
Information Number
Data Unit
General Interrogation

Table of Contents