List of information - Central Unit
365
7SS52 V4 Manual
C53000-G1176-C182-1
FNo. Description Function Type
ofIn-
for-
matio
n
Log-Buffer Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information No.
Data Unit
General Interrogation
3 >Synchronize Internal Real Time
Clock (>Time Synch)
Device SP_E
v
* * LED BI BO 135 48 1 no
4 >Trigger Waveform Capture
(>Trig.Wave.Cap.)
Osc. Fault Rec. SP on * m LED BI BO 135 49 1 yes
5 >Reset LED (>Reset LED) Device SP on * * LED BI BO 135 50 1 yes
15 >Test mode (>Test mode) Device SP on
off
* * LED BI BO 135 53 1 yes
16 >Stop data transmission (>Data-
Stop)
Device SP on
off
* * LED BI BO 135 54 1 yes
51 Device is Operational and Protec-
ting (Device OK)
Device OUT on
off
* * LED BO 135 81 1 yes
55 Reset Device (Reset Device) Device OUT on * * LED BO
56 Initial Start of Device (Initial Start) Device OUT on * * LED BO 194 5 1 no
60 Reset LED (Reset LED) Device OUT_
Ev
67 Resume (Resume) Device OUT on * * LED BO 135 97 1 yes
68 Clock Synchronization Error
(Clock SyncError)
Device OUT on
off
* * LED BO 135 202 1 yes
69 Daylight Saving Time (DayLight-
SavTime)
Device OUT on
off
**LEDBO
70 Setting calculation is running
(Settings Calc.)
Device OUT on
off
* * LED BO 194 22 1 yes
71 Settings Check (Settings Check) Device OUT * * * LED BO
72 Level-2 change (Level-2 change) Device OUT on
off
**LEDBO
73 Local setting change (Local
change)
Device OUT * * * LED BO
95 Setting change in progress
(Change in Prog.)
Device OUT * * * LED BO
110 Event lost (Event Lost) Device OUT_
Ev
on * * LED BO 135 130 1 no
113 Flag Lost (Flag Lost) Device OUT on * m LED BO 135 136 1 yes
203 Waveform data deleted (Wave.
deleted)
Osc. Fault Rec. OUT_
Ev
on * LED BO 135 203 1 no
301 Power System fault
(Pow.Sys.Flt.)
Device OUT on
off
on * LED BO 135 231 2 yes
302 Fault Event (Fault Event) Device OUT * on * LED BO 135 232 2 yes
303 Earth fault (Earth Fault) Device OUT on
off
* K * LED BO
320 Warn: Limit of Memory Data ex-
ceeded (Warn Mem. Data)
Device OUT on
off
**LEDBO
321 Warn: Limit of Memory Parameter
exceeded (Warn Mem. Para.)
Device OUT on
off
**LEDBO
322 Warn: Limit of Memory Operation
exceeded (Warn Mem. Oper.)
Device OUT on
off
**LEDBO
323 Warn: Limit of Memory New ex-
ceeded (Warn Mem. New)
Device OUT on
off
**LEDBO
10410 Diff-current superv. CZ (group
alarm) (Id-sup CZ M)
Monitoring OUT * * * LED BO 194 205 1 yes
10411 Diff-current supervision Check
Zone L1 (Id-sup CZ L1)
Monitoring OUT on
off
* * LED BO 194 206 1 yes
10412 Diff-current supervision Check
Zone L2 (Id-sup CZ L2)
Monitoring OUT on
off
* * LED BO 194 207 1 yes