Mounting and maintenance
4.2 Rail mounting
Power supply system SITOP PSU8600
120 Manual, 09.2018, A5E36758446-5-76
All additional supplementary modules can be connected in the same way to the
supplementary module to the left.
Note
The power supply system can be
mounted in a control cabinet on standard mounting rails
60715. For stability reasons, it is recommended that the TH35-15 version
mm deep) is used. The TH35-7.5 (7.5 mm deep) version has been released for use with
m. However, when installing the standard mounting rail with a depth
mm, it is crucial that a suitable number of mounting points (dependent on the system
configuration and therefore the total weight) is used so that the standard mounting rail does
no
t twist.
Note
Installation of the unit in a hazardous zone
Not permissible for 6EP4143
-8JB00-0XY0 (LiFePO4 264 Wh)
If the unit is to be used in a potentially explosive environment (II 3G nA IIC T4 Gc), it must be
installed in a distri
butor box with degree of protection IP54 or higher. This distribution box
must comply with the requirements of EN 60079
-15 and must require a tool for opening.