Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
322 Manual, 09.2018, A5E36758446-5-76
7.8.6.7
Hardware
Display name
Data type
Definition
Description
HardwareManRemoteDipSwitch Boolean PropertyType REMOTE operating mode is se-
lected.
HardwareOperatingModeDipSwitch Boolean PropertyType Actual switch position operating
mode output 1 at the basic unit
constant current or electronic shut-
down.
HardwarePriorityBufferedChan-
nel1DipSwitch
Boolean PropertyType Actual switch position for prioritized
buffering (PRIO) of output 1 at the
basic unit
HardwareReservedDipSwitch
Boolean
PropertyType
-
HardwareResetInput
Boolean
PropertyType
Actual state of input "RST"
HardwareStartupModeDipASwitch Boolean PropertyType Actual switch position for the sys-
tem switch-on behavior, dip
switch 1
HardwareStartupModeDipBSwitch Boolean PropertyType Actual switch position for the sys-
tem switch-on behavior, dip
switch 2
HardwareWebserver
EnableDipSwitch
Boolean PropertyType Web server is enabled MANUALLY
7.8.6.8
Identification
Display name
Data type
Definition
Description
IdentificationDeviceNameSetpoint
String
PropertyType
PROFINET device name
IdentificationContactSetpoint
String
PropertyType
Contact person
IdentificationLocationSetpoint String PropertyType Location
IdentificationPNLocationIDSetpoint
String
PropertyType
Location ID
IdentificationPNPlantDesigna-
tionSetpoint
String PropertyType System designation
Note
Parameter "IdentificationPlantDesignationSetpoint" and "IdentificationLocationSetpoint" are
handled differently by the various S7 systems.
S7
-1200 and S7-1500 correctly process the data sets.
S7
-300, S7-400 and ET200SP do not fully support this data. Proceed as follows to correctly
save this data to these PLCs:
Write the data to identify the devices in the PLC code using function "WR_REC".
Read the data to identify the devices using "RD_REC".
For the ET200SP, a description of the two functions can be found here
(https://support.industry.siemens.com/cs/de/en/view/58649293
):
Alternatively, use the PRONETA
(
https://support.industry.siemens.com/cs/ww/en/view/67460624) tool to read and write
data