Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
316 Manual, 09.2018, A5E36758446-5-76
UpdateProgress UInt32 AnalogItemType Firmware update progress
UpdateState UInt32 AnalogItemType Status or result of the ongoing or
completed firmware update:
0: Firmware is being updated
1: The file download was exited,
the system must be restarted to
initiate the internal update process.
2: The data format of the update
file was not accepted.
3: The update file is too big.
4: The update file does not match
this device.
5: The device is in the buffer mode,
and cannot be updated at the pre-
Alarm_F_CommunicationToModule Boolean Sitop_8600_AlarmType There is a communication error on
the internal communication bus to
the expansion modules. The out-
puts at the modules that cannot be
accessed are switched off.
Alarm_F_CommunicationToPrimary Boolean Sitop_8600_AlarmType There is a communication error to
the primary supply unit. All outputs
Alarm_F_CommunicationToSystem Boolean Sitop_8600_AlarmType The alarm signals that there is a
communication error between the
Profinet module and the main con-
troller.
Alarm_F_DeviceOvertemperature Boolean Sitop_8600_AlarmType Overtemperature condition in a part
of the device. The temperature lies
above the safety threshold. The
device or the channel is shut down
Alarm_F_ExtensionModuleNotAvailable Boolean Sitop_8600_AlarmType The expansion module was not
able to be found. Error in the con-
figuration. The system responds
differently depending on the con-
Alarm_F_General Boolean Sitop_8600_AlarmType General critical error. All outputs
Alarm_F_IncompatibleModuleDetected Boolean Sitop_8600_AlarmType Incompatible expansion module
Alarm_F_ModuleDefect Boolean Sitop_8600_AlarmType Module failure