Display name
Data type
Definition
Description
Alarm_F_ModuleParametersCorrupt Boolean Sitop_8600_AlarmType The stored module configuration is
corrupt. The module cannot start
up correctly.
Alarm_F_Phasefail Boolean Sitop_8600_AlarmType A phase failure due to the failure of
a supply cable is outside the load
or time profile. This means that all
outputs are switched off.
Alarm_F_RestartAfterCriticalCurrent Boolean Sitop_8600_AlarmType After an automatic shutdown due to
a critically high-voltage, the device
is ready to be started again. Reac-
tivate the device by switching off
the input voltage and then recon-
necting it.
Alarm_F_RestartAfterPeakload Boolean Sitop_8600_AlarmType After an automatic shutdown due to
a load peak, the device is ready to
be started again.
Alarm_F_SafetyErrorOffLoadCheck Boolean Sitop_8600_AlarmType Critical load difference between the
input and the outputs. The device
is shut down.
Alarm_F_SafetyShutdownLoadCheck Boolean Sitop_8600_AlarmType Load difference between the input
and outputs lies outside the per-
missible limits. Reactivate the sys-
tem by switching off the device and
switching it on again.
Alarm_F_SoftwareUpdating Boolean Sitop_8600_AlarmType New firmware is presently being
loaded to the system. Read-
ing/writing general unit data is
presently not possible.
Alarm_F_Supplylimits Boolean Sitop_8600_AlarmType The supply voltage is outside the
defined maximum values. The
outputs are switched off.
Alarm_F_SystemDefect Boolean Sitop_8600_AlarmType Unclassified hardware fault in the
system. All system outputs are
switched off.
Alarm_F_Systemoverload Boolean Sitop_8600_AlarmType The system load is outside the
defined overload profile (either
because of the magnitude or be-
cause the time was excessively
long). The outputs of the channel
expansions are shut down.
Alarm_F_SystemParametersCorrup Boolean Sitop_8600_AlarmType The system configuration is defec-
tive/false. System operation is not
possible.
Alarm_F_UnexpectedEmptySlotDetected Boolean Sitop_8600_AlarmType Not all of the configured expansion
modules were identified.
Alarm_F_UnknownModuleDetected
Boolean
Sitop_8600_AlarmType
Unknown module found.
Alarm_F_UnknownModuleDetectedSlot1
Boolean
Sitop_8600_AlarmType
Unknown module found (slot 1).
Alarm_F_UnknownModuleDetectedSlot2
Boolean
Sitop_8600_AlarmType
Unknown module found (slot 2).
Alarm_F_UnknownModuleDetectedSlot3
Boolean
Sitop_8600_AlarmType
Unknown module found (slot 3).
Alarm_F_UnknownModuleDetectedSlot4
Boolean
Sitop_8600_AlarmType
Unknown module found (slot 4).