Safety, approvals, EMC
10.2 Test voltages
Power supply system SITOP PSU8600
406 Manual, 09.2018, A5E36758446-5-76
Figure 10-1 Test voltage without auxiliary contact diagram
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
● Connect the input terminals with one another
● Connect the output terminals with PE
Test (C)
● Connect the output terminals with one another and measure with respect to PE
Table 10- 1 Test voltage
Type test
Production test
Field test
Tripping current for DC measurement: 0
mA
Tripping current for AC measurement: < 100 mA