EasyManua.ls Logo

Siemens SITOP PSU8600 - Page 154

Siemens SITOP PSU8600
420 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
6.1 Line-side connection
Power supply system SITOP PSU8600
154 Manual, 09.2018, A5E36758446-5-76
Protection
Protection 6EP3436-8MB00-2CY0
Protection
required
3-pole coupled miniature circuit breaker (IEC 898) characteristic C, 6 - 16 A
or
3RV2011-1DA10 circuit breaker, setting of the thermal overcurrent release: 3 A
or
3RV2711-1DD10 circuit breaker (branch circuit protection acc. to UL489-listed,
DIVQ)
Protection 6EP3437-8MB00-2CY0
Protection
required
3-pole coupled miniature circuit breaker (IEC 898) characteristic C, 10 - 16 A
or
3RV2011-1DA10 circuit breaker, setting of the thermal overcurrent release: 3 A
or
3RV2711-1DD10 circuit breaker (branch circuit protection acc. to UL489-listed,
DIVQ)
The protective conductor of the line supply must be connected at the "PE" terminal.
Additional information is provided in Chapter "Connections and terminal designations
(Page 32)".