Installation
6.8 Connecting battery modules to the UPS module
Power supply system SITOP PSU8600
166 Manual, 09.2018, A5E36758446-5-76
Proceed as follows, to connect several BAT8600 battery modules:
1. Connect several battery modules in parallel to the power terminals
① and the UPS
module to the communication terminals
②.
Figure 6-2 Recommended wiring for up to 5 battery modules connected in parallel
2. Insert the reserve fuses ⑦.
3. Check that the wiring is correct.
4. Insert the fuses
③
The connected battery modules are automatically identified after several seconds.
Danger due to high short-circuit current
Before inserting the fuses, check the correct polarity of the wiring of all of the connected
battery modules.