Engineering and remote access
7.5 SIMATIC STEP 7
Power supply system SITOP PSU8600
212 Manual, 09.2018, A5E36758446-5-76
Subgroup
Description
Output 1 In these subgroups, make the following settings for the individual outputs:
Switch-on and switch-off output.
Setpoint output voltage
Response threshold value of the output current
Define a threshold for the output of an alarm.
An alarm is output if this threshold is continually exceeded for 5 ms.
Define the on delay.
Specify the operating mode:
ELECTRONIC SHUTDOWN or CONSTANT CURRENT
Web server
Activate web server on this module.
Enable automatic update
Update interval
Enable automatic logoff
Permit access only with HTTPS
A detailed description of the individual parameters of the subgroups is provided in Sections
"Parameterizing the basic unit (Page 213)" and "Parameterizing output 1 (Page 219)".
Parameters of the expansion modules
Subgroups "Output 1n" are relevant when parameterizing expansion modules.
Subgroup
Description
Output 1 … n In these subgroups, make the following settings for the individual outputs:
Switch-on and switch-off output.
Setpoint output voltage
Response threshold value of the output current
Define a threshold for the output of an alarm.
An alarm is output if this threshold is continually exceeded for 5 ms.
Define the on delay.
Define the operating mode:
ELECTRONIC SHUTDOWN or CONSTANT CURRENT.
A detailed description of the individual parameters of the subgroups is provided in Section
"Parameterizing output 1 (Page 219)".
Parameters of buffer modules with electrolytic capacitors
With the exception of the standard settings for IO devices, the buffer modules with
electrolytic capacitors have no configurable parameters.
Parameters of buffer modules with double-layer capacitors
BUF8600 4s/40A
(6EP4293-8HB00-0XY0)
BUF8600 10s/40A
(6EP4295-8HB00-0XY0)
For the parameterization of buffer modules with double-layer capacitors, under the
"Properties" tab for the basic unit select the "Buffering" subgroup.