Engineering and remote access
7.5 SIMATIC STEP 7
Power supply system SITOP PSU8600
218 Manual, 09.2018, A5E36758446-5-76
Note
Response for a PROFIenergy pause:
As soon as the command to s
tart a PROFIenergy pause is issued via PROFINET, the
operating status of the outputs cannot be influenced using switch
-on or shutdown
commands, which are sent in the REMOTE operating mode during the PROFIenergy pause.
These commands are buffered up to the
end of the PROFIenergy pause.
The configuration of the outputs is automatically updated as soon as the command to exit
the PROFIenergy pause is issued. All of the switch
-on and shutdown commands that
occurred during the PROFIenergy pause are taken into ac
count.
All other commands are immediately executed, even during a PROFIenergy pause.
PROFIenergy output parameters
The outputs are selected using a binary number, which is converted into a decimal value.
Binary number 1111101001 is converted into decimal value 1001.
Outputs that can be switched off for a
0 … 8.589.934.591
0
*maximum value for 33 outputs
Activate web server on this module
0 / 5 s / 10 s / 20 s / 30 s / 60 s
Permit access only with HTTPS