Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
253
Index 48: PROFIenergy values (reading/writing)
PROFIenergyEnabled (0/255)
Enable PROFIenergy on this device
Fill byte(s) - 3xUnsigned8
TimeToPause [ms] Time that elapses up to the start of PROFIenergy
Unsigned32
TimeToOperate [ms] Time that elapses up to the start of operation Unsigned32
SavingPowerConsumption [kW] Power consumption in the energy-saving mode
Float
OperatePowerConsumption [kW]
Power consumption in operation [kWh]
EnergyConsumptionToPause [kWh]
Power drawn up to the start of the pause [kWh]
EnergyConsumptionToOperate [kWh]
Power drawn up to the start of operation [kWh]
Index 49: PROFIenergy channel list (reading/writing)
ChannelsOffList Overview of the outputs that are switched off. Each
output is represented using 1 bit (starting with bit 0
Unsigned64
Index 53: Web server (reading/writing)
WebserverEnabled Activating/deactivating the web server of the
SITOP PSU8600:
• 0: disable
• 255: enable
Unsigned8
AutoReloadEnabled Enable/disable automatic update:
• 0: disable
• 255: enable
Unsigned8
ReloadTime Update interval:
• 0: Off
• 5: 5s
• 10: 10s
• 20: 20s
• 30: 30s
• 60: 60s
Unsigned8