Engineering and remote access
7.7 Web server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
299
Switch on output Yes/no No
Response threshold of the output current
Prewarning threshold output current
On delay Dependent on the settings in
the basic unit
None
Operating mode ELECTRONIC
SHUTDOWN / CONSTANT
ELECTRONIC
SHUTDOWN
●
Here, you specify whether the output is switched on.
●
Define the required output voltage.
Using the "MANUAL >> REMOTE" button you load the value set using the potentiometer
at the front of the device into the REMOTE configuration of the system. If the button is
grayed out, this means that there is a connection to a control system.
●
Response threshold of the output current
Define the required response threshold value of the output current for the particular
output.
Using the "MANUAL >> REMOTE" button you load the value set using the potentiometer
at the front of the device into the REMOTE configuration of the system. If the button is
grayed out, this means that there is a connection to a control system.
●
Prewarning threshold output current
Using prewarning thresholds for the output current of the individual outputs, you can
identify at an early stage slight (creeping) changes in the current demand of the
connected load. This prewarning secures the highest possible availability of the system
(maintenance).
Enter a value of "0 %" to deactivate the prewarning threshold.