Engineering and remote access
7.7 Web server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
301
Configuring UPS8600
Parameters of the UPS module
Maximum charging power
Select between "High" and "Low".
The charging power can be reduced from the preset 120 W to 60 W to reduce the effect
of the charging power on the power that is available at the outputs. In this way, the UPS
module can be adapted to power supply systems with a total output power of 480 W.
Battery test interval
Select at which time intervals the battery test should be performed.
Buffer timer enabled
Shows whether the buffer timer is activated
Maximum buffer time
Maximum buffering time.
Configuring BAT8600
Battery modules do not have to be configured.