Engineering and remote access
7.10 Parameter write behavior of the SITOP PSU8600
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
349
Cyclic communication is blocked or is not accepted if the control is not in the RUN mode.
Only functional settings are available via cyclic data. General settings are not part of the cyclic data set.
General settings are always retentively written.
Functional settings and results of online functions are saved in a volatile fashion if the control is in the RUN mode.
Cyclic data never change retentive settings.
General settings are always retentively written via OPC UA.
Volatile functional settings are retentively saved using the OPC UA SAVE function.
Only online functions