Troubleshooting
8.2 PROFINET alarm list
Power supply system SITOP PSU8600
362 Manual, 09.2018, A5E36758446-5-76
Channel
Error Type
Extended
Error Type
Severity
Alarm text
Help text
259 16 N Buffer component disabled via
control contact
Buffer component disabled via control contact
259
17
N
Battery SoH test
Battery 'State of Health' tests (SoH) are performed.
259 18 N Buffer timer exceeded, system
is turned off.
Buffer time exceeded, the system is switched off
259 19 MR Buffering mode not possible
due to low charge level
Buffers empty, buffering not possible
259 20 MR Insufficient charge level The battery charge level is too low to guarantee the
configured buffer capacity.
259 21 N Buffer component disabled via
control command
Buffer module has been disabled REMOTELY.
259 23 MR Communication to battery inter-
rupted (slot 1)
259 24 MR Communication to battery inter-
rupted (slot 2)
259 25 MR Communication to battery inter-
rupted (slot 3)
259 26 MR Communication to battery inter-
rupted (slot 4)
259 27 MR Communication to battery inter-
rupted (slot 5)
259 28 N Charging restricted due to sys-
tem overload
Charging of the system buffering components has
been limited due to system overload.
259 29 N After multiple buffering of a
system overload, the safety
buffer extension was activated.
1 minute buffering extension after third buffering
event is running.
259 30 N Charging power reduced due
high system load
The charging power has been reduced below its
target value due to high system load.
259 31 N Charging disabled due high
system load
The charging has been disabled due high system
load. Charging will continue automatically when free
system load is available again.
259 32 N Battery capacity tracing test
canceled. Not fully charged
batteries
The battery capacity tracing test cannot be started
because of not fully charged batteries.
259 33 N Battery capacity tracing test
canceled. Insufficient system
load
The battery capacity tracing test is canceled because
of insufficient system load.
259 34 N Battery capacity tracing test
canceled by user
The battery capacity tracing test is canceled by the
user
259 35 N Battery capacity tracing test
canceled. Buffering started
The battery capacity tracing test is canceled because
of started buffering mode.
259 36 N Battery capacity tracing test
canceled. Input voltage too high
The battery capacity tracing test is canceled because
of too high input voltage.
260 1 F Faulty communication to the
module.
Communication with the expansion module is faulty. All
outputs on the expansion module have been switched off.