Troubleshooting
8.3 Alarm list web server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
379
Different firmware version detected
Different firmware version detected
47 MR New unconfigured module detect-
ed.
New unconfigured module detected.
Different serial number detected
Different serial number detected
49 MR Module with excessive power de-
A module with excessive power was detected. Normal oper-
ation of the system is possible.
Unexpected module type detected.
Unexpected module type detected.
51 MD Module with reduced power de-
A module with reduced power was detected. Deviating sys-
tem behavior may be possible.
52 F Incompatible module detected. The module has a module type that is incompatible with the
configuration. The module cannot be commissioned.
Unexpected empty slot detected.
Unexpected empty slot detected.
54 MD Battery not available Attempt to access a battery that is not available. Either the
battery with the requested number was never connected or
communication with this battery was interrupted.
58 N Buffer component disabled via
Buffer component disabled via control contact
Wrong battery polarity - check battery connections.
60 MR Communication to battery inter-
rupted
Communication with the battery is interrupted. Buffering is
still possible, but the battery charge is reduced to a mini-
61 MR Power connection to battery inter-
rupted
Power connection to at least one battery interrupted. Check
power connection and fuse.
Battery 'State of Health' tests (SoH) are performed.
63 N Buffer timer exceeded. Buffer timer exceeded, system is turned off.
64 MD Wrong battery configuration (bat-
Different battery types connected. Only batteries of the
same type can be operated together.
65 MR Surplus battery More than 6 batteries are connected. Connect a maximum
of 6 batteries to the Energy Storage Link.
66 MR Battery on subslot 1 disconnected
67 MR Battery on subslot 2 disconnected
68 MR Battery on subslot 3 disconnected
69 MR Battery on subslot 4 disconnected
70 MR Battery on subslot 5 disconnected
71 N Buffering extension activated 1 minute buffering extension after third buffering event is
72 N Charging power reduced due to
high system load
The charging power has been reduced below its target val-
ue due to high system load.
73 N Charging disabled due to high
system load
The charging has been disabled due to high system load.
Charging will continue automatically when free system load