Troubleshooting
8.3 Alarm list web server
Power supply system SITOP PSU8600
382 Manual, 09.2018, A5E36758446-5-76
Alarm list, battery modules from third-party manufacturers
The IDs for the BAT8600 module alarms depend on the number of the particular battery
module:
Battery 1: 100 + ID
Battery 2: 130 + ID
Battery 3: 160 + ID
Battery 4: 190 + ID
Battery 5: 220 + ID
ID
Severity
Event
Help text
2
MR
New battery detected
New battery detected
3 MD Unknown battery Data cannot be read correctly from the battery. Battery is
defective or not supported by SIEMENS.
6
MR
Unexpected module type detected.
Unexpected module type detected.
9 N Battery discharged Battery is discharged - no buffering possible.
10
MR
Deep discharge battery
Battery is deep discharged - no buffering possible.
11 MD Battery defective Battery defective - neither buffer nor charging operation is
possible
20 MD Battery parameters corrupt The battery configuration is corrupt. Battery behavior may
deviate.
21 MR Battery parameters corrupt The battery configuration is corrupt. The battery behavior
remains unchanged, however.
23 MR The power line to the battery is
interrupted.
The power line to the battery is interrupted. The battery can
no longer buffer or it can no longer be charged any more.