Technical data
9.2 Output data
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
387
Expansion module
6EP4436-8XB00-0CY0
Expansion module
6EP4437-8XB00-0CY0
Expansion module
6EP4436-8XB00-0CD0
Regulated, isolated DC voltage
Rated output voltage
U
out rated
DC
24 V 24 V 24 V
Total tolerance, static ±
Static line regulation, ap-
0.2 % 0.2 % 0.2 %
Static load regulation, ap-
0.1 % 0.1 % 0.1 %
Residual ripple in the load
range
100 mV 100 mV 100 mV
Spikes peak-peak, max.
(bandwidth, approx.
200 mV 200 mV 200 mV
Adjustment range
• Comment
4 - 28 V
Derating > 24 V: 4 % I
out
/V
4 - 28 V
Derating > 24 V: 4 % I
out
/V
4 - 28 V
Derating > 24 V: 4 % I
out
/V
Output voltage adjustment Via potentiometer
or in the REMOTE operating
Via potentiometer
or in the REMOTE opera-
Via potentiometer
or in the REMOTE opera-
Operating display 3-color LED for the module
operating status;
3-color LED per output for the
output operating status
3-color LED for the module
operating status;
3-color LED per output for
the output operating status
3-color LED for the module
operating status;
3-color LED per output for
the output operating status
Via relay contact, basic unit
Via relay contact, basic unit
Via relay contact, basic unit
Switch-on/switch-off behav-
ior
No overshoot of U
out
(Soft-Start)
Rise time of the output
500 ms 500 ms 500 ms
Switching on outputs In conjunction with CNX8600 expansion module: all outputs are simultaneously switched-on
after the device powers up, after a delay time of 25 ms, 100 ms – or "load optimized" where
the outputs are sequentially switched-on, can be selected via DIP switch
Rated output current I
out rated
2)
2)
2)
Current range 0 - 20 A
2)
0 - 40 A
2)
0 - 20 A
2)
Output current per output 5 A
2)
10 A
2)
2.5 A
2)
Output active power (typi-
480 W
2)
960 W
2)
480 W
2)
Using the SITOP CNX8600 expansion module it is not possible to increase the maximum output power of the complete