Description, device design, dimension drawing
2.8 Display elements
Power supply system SITOP PSU8600
48 Manual, 09.2018, A5E36758446-5-76
Table 2- 10 LED "ON/OFF/RST"
Signaling
Off
Device is OFF or is powering up (booting)
Or ERROR OFF shutdown
Or incorrect hardware configuration (REMOTE operating mode)
or firmware being updated/completed.
Green
Normal operation, output current < response threshold value
Flashing green (0.25/0.25) Overload at the output: Output current 101 - 150 % of the response threshold
up to 149 %: operation permissible for 5 s, 150 %: operation permissible for
200 ms
Flashing green (1/1) For overload, the output current is limited
To the response threshold value for the duration of the overload (
CONSTANT CURRENT operating mode)
to the rated value for 60 s for system overload
Red Output automatically switched off due to
Overload exceeding the permissible time range ( ELECTRONIC
SHUTDOWN operating mode)
Overtemperature of the output
Flashing red (0.25/0.25)
After automatic shutdown due to overload or overtemperature, output is ready for
reset by pressing the button, reset signal or control command
Flashing red (1/1)
Output switched off via control command (REMOTE mode)
Yellow
Output manually switched off using the button at the device