Description, device design, dimension drawing
2.8 Display elements
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
53
States of the individual LEDs
Table 2- 13 LED "O.K."
Signaling
Off
Device is OFF or is powering up (booting)
Green
Normal operation, module charged, complete buffer readiness
Flashing green (1/1)
Module is being charged, buffer readiness partially available.
Flashing green (0.25/0.25)
Module is being charged, buffer readiness not available
Red
ERROR OFF: Module automatically switched off due to overtemperature
basic unit, phase imbalance
Fault in the module or communication error to the basic unit
flashing red (1/1)
Module deactivated via ON/OFF contact or remote command (no buffering when
the power fails)
Flashing red (0.25/0.25)
Module ready for the automatic ERROR OFF shutdown to be reset or after
a firmware update has been completed, by switching off the supply voltage
and switching it on again (power OFF/ON)
Charge is still available after power supply voltage OFF
Device shut down due to firmware update of another system component
Incorrect hardware configuration (REMOTE mode)
Yellow
Power failure, buffer mode active
Alternating, green/red
(0.25/0.25)
Firmware being updated