Page 46 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS 7ML1998MV01
mmmmm
Commissioning
Maximum Volume
The maximum volume of the vessel. Enter the vessel volume corresponding to the
High Calibration Point. For example, if your maximum vessel volume is 8000 L, enter a
value of 8000.
End of QS Volume Wizard
For QS to be successful, all changes must be applied.
To transfer Quick Start values to the device and return to Program menu, press
DOWN arrow (Finish). Then press LEFT arrow three times to return to
Measurement mode.
Value
Range: 0.0 to 9999999
Default: 100.0
Options
BACK, CANCEL, FINISH (Display returns to 1.1 Quick Start menu when Quick
Start is successfully completed or cancelled. If CANCEL is selected, no
changes are written to the device.)